Design and development of refrigerated chamber for blood plasma at-40 C

Abstract

The purpose of the project is the design and implement of two stage vapor compression refrigeration cycle with intermediate vessel and double throttling , for storage of 10 kg of frozen plasma ; that used in medical applications , and save it at -35 ˚C refrigeration space. The refrigerant R404A was selected as suitable working fluid . This system consists of two cycles connected in series , where the higher cycle operates between (-8 and 45 ˚C), and the low cycle operates between (-45 and -8 ˚C). Full theoretical design and building of the system will be made , including the full automation for the cycle and controlling of it’s componants.

Description

CD , no of pages 73 ,26821 , ميكانيك 5/2013 , in the store ,

Citation

Endorsement

Review

Supplemented By