BaseRdc(Ohm/kft or Ohm/km) = 0.0072
TcAdj = 1.25025
RdcT_Adj(Ohm/kft or Ohm/km) = 0.0090018
RShield = 275.885
Yshield_Circ = 0, Yshield_Eddy = 0.00297396
MF = 1, Ycs = 0.0879459, Ycp = 0.00980412, YsShield = 0.00297396, YsSheath = 0, YsShield/Sheath = 0,Ys (Shield + Sheath + Shield/Sheath) = 0.00297396, YsArmor = 0, Yconduit = 0
Rac/Rdc(1.10072) = [1 + MF(1) * (Ycs(0.0879459) + Ycp(0.00980412) + Yshield(0.00297396) + Ysheath(0)) + Yconduit(0)] * (1 + Yarmor(0))
RacT_Adj(Ohm/kft or Ohm/km) = 0.0099085
RL'(Ohm/kft or Ohm/km) = 0.0099085
Delta(m) = 348.282
Case1: 3 x 1/C unshielded/unsheathed and unarmoured cable with no Main or Aux N or PE wires as per cases 1a & 1b of IEC 60909-2 Table 7 (TT system)
X1 Factor = 1
Unit Conversion Factor = 0.3048